When we talk about how well a transformer performs, we often use the term 'efficiency.' But for transformers that are continuously connected to the power grid, especially those distributing electricity to our homes and businesses, a simple efficiency number at full load doesn't tell the whole story. This is where All-Day Efficiency becomes incredibly important. Imagine the transformer on the pole outside your house. It's working 24 hours a day, every day, right? But the amount of electricity it's delivering, its 'load,' changes drastically throughout the day. People are using more power in the morning, less during the afternoon when they're at work, and then more again in the evening. All-day efficiency is designed to capture this dynamic reality.
So, what is it exactly? All-day efficiency is defined as the ratio of the total energy the transformer delivers to the load over a full 24-hour period, divided by the total energy it takes in from the grid during that same 24 hours. We measure this energy in kilowatt-hours, or kWh. Unlike conventional efficiency, which gives you an instantaneous snapshot, all-day efficiency provides a comprehensive view of how energy-efficient the transformer truly is over an extended operational cycle.
Think of your car's fuel efficiency. If you only measure it on a long highway trip, you might get excellent miles per gallon. But if you also consider all the time you spend in stop-and-go city traffic, or idling in a parking lot, your average fuel efficiency over a whole week will be much lower. All-day efficiency is like calculating that average fuel efficiency for a transformer over 24 hours, including all its "idling" and "peak traffic" moments.
\--
\--
Learn essential terms and foundational ideas that form the basis of the topic.
Key Concepts
Definition: Ratio of total energy output to total energy input over 24 hours.
Relevance: Crucial for distribution transformers operating with fluctuating loads 24/7.
Distinction from Conventional Efficiency: Accounts for continuous core losses (24 hours) and variable copper losses (only when loaded).
Calculation: Requires detailed load profile (percentage load and duration).
Formula Components: Sum of Energy Output, Total Core Energy Loss ($P\c \times 24 \text{ hrs}$), and Total Copper Energy Loss (sum of $x^2 P\{cu,FL} \times \text{hrs}$ for each load period).
Practical Implication: Guides selection of transformers optimized for minimum lifetime energy consumption, often prioritizing lower core losses.
Scenario for Calculation: A 100 kVA distribution transformer has $P\c = 500 \text{ W}$ and $P\{cu,FL} = 1000 \text{ W}$.
It operates at 75% full load for 10 hours at 0.8 PF lagging.
It operates at 50% full load for 8 hours at 0.7 PF lagging.
It operates at 20% full load for 6 hours at 0.6 PF lagging.
Core Energy Loss (24 hrs): $0.5 \text{ kW} \times 24 \text{ hrs} = 12 \text{ kWh}$.
Copper Energy Loss (24 hrs):
Period 1: $(0.75)^2 \times 1 \text{ kW} \times 10 \text{ hrs} = 0.5625 \times 10 = 5.625 \text{ kWh}$
Period 2: $(0.5)^2 \times 1 \text{ kW} \times 8 \text{ hrs} = 0.25 \times 8 = 2 \text{ kWh}$
Period 3: $(0.2)^2 \times 1 \text{ kW} \times 6 \text{ hrs} = 0.04 \times 6 = 0.24 \text{ kWh}$
Total Copper Energy Loss: $5.625 + 2 + 0.24 = 7.865 \text{ kWh}$.
Output Energy (24 hrs):
Period 1: $100 \text{ kVA} \times 0.75 \times 0.8 \text{ PF} \times 10 \text{ hrs} = 600 \text{ kWh}$
Period 2: $100 \text{ kVA} \times 0.5 \times 0.7 \text{ PF} \times 8 \text{ hrs} = 280 \text{ kWh}$
Period 3: $100 \text{ kVA} \times 0.2 \times 0.6 \text{ PF} \times 6 \text{ hrs} = 72 \text{ kWh}$
Total Output Energy: $600 + 280 + 72 = 952 \text{ kWh}$.
All-Day Efficiency: $\frac{952 \text{ kWh}}{952 \text{ kWh} + 12 \text{ kWh} + 7.865 \text{ kWh}} \times 100% = \frac{952}{971.865} \times 100% \approx 98.05%$.
Design Choice: A utility needs a transformer for a residential area. Transformer A has 98% full-load efficiency but high core losses. Transformer B has 97.5% full-load efficiency but very low core losses. Transformer B is likely to have higher all-day efficiency and be a better choice, as residential loads are highly fluctuating.
Term: All-Day Efficiency
Definition: Measures transformer efficiency based on total energy output vs. input over 24 hours.
Term: Distribution Transformer
Definition: Key application for all-day efficiency, as they operate continuously with varying loads.
Term: Load Cycle
Definition: The pattern of load variation on a transformer throughout a typical day.
Term: Constant Losses
Definition: Core losses, which occur 24/7 regardless of the transformer's load.
Term: Variable Losses
Definition: Copper losses, which depend on the square of the load current and are negligible at no-load.
"Average" Efficiency: Think of all-day efficiency as the "average" efficiency, not just the peak efficiency. It's the total energy over a long period.
"24/7" Transformers: It's for transformers that are always on, even when not working hard.
Losses Add Up: Core losses are like a fixed monthly fee (always there), while copper losses are like a variable usage charge (only when you use it). All-day efficiency sums up both.
Energy vs. Power: Remember it's about energy (kWh) over time, not just instantaneous power (kW).
See how the concepts apply in real-world scenarios to understand their practical implications.
Scenario for Calculation: A 100 kVA distribution transformer has $P\c = 500 \text{ W}$ and $P\{cu,FL} = 1000 \text{ W}$.
It operates at 75% full load for 10 hours at 0.8 PF lagging.
It operates at 50% full load for 8 hours at 0.7 PF lagging.
It operates at 20% full load for 6 hours at 0.6 PF lagging.
Core Energy Loss (24 hrs): $0.5 \text{ kW} \times 24 \text{ hrs} = 12 \text{ kWh}$.
Copper Energy Loss (24 hrs):
Period 1: $(0.75)^2 \times 1 \text{ kW} \times 10 \text{ hrs} = 0.5625 \times 10 = 5.625 \text{ kWh}$
Period 2: $(0.5)^2 \times 1 \text{ kW} \times 8 \text{ hrs} = 0.25 \times 8 = 2 \text{ kWh}$
Period 3: $(0.2)^2 \times 1 \text{ kW} \times 6 \text{ hrs} = 0.04 \times 6 = 0.24 \text{ kWh}$
Total Copper Energy Loss: $5.625 + 2 + 0.24 = 7.865 \text{ kWh}$.
Output Energy (24 hrs):
Period 1: $100 \text{ kVA} \times 0.75 \times 0.8 \text{ PF} \times 10 \text{ hrs} = 600 \text{ kWh}$
Period 2: $100 \text{ kVA} \times 0.5 \times 0.7 \text{ PF} \times 8 \text{ hrs} = 280 \text{ kWh}$
Period 3: $100 \text{ kVA} \times 0.2 \times 0.6 \text{ PF} \times 6 \text{ hrs} = 72 \text{ kWh}$
Total Output Energy: $600 + 280 + 72 = 952 \text{ kWh}$.
All-Day Efficiency: $\frac{952 \text{ kWh}}{952 \text{ kWh} + 12 \text{ kWh} + 7.865 \text{ kWh}} \times 100% = \frac{952}{971.865} \times 100% \approx 98.05%$.
Design Choice: A utility needs a transformer for a residential area. Transformer A has 98% full-load efficiency but high core losses. Transformer B has 97.5% full-load efficiency but very low core losses. Transformer B is likely to have higher all-day efficiency and be a better choice, as residential loads are highly fluctuating.
Term: All-Day Efficiency
Definition: Measures transformer efficiency based on total energy output vs. input over 24 hours.
Term: Distribution Transformer
Definition: Key application for all-day efficiency, as they operate continuously with varying loads.
Term: Load Cycle
Definition: The pattern of load variation on a transformer throughout a typical day.
Term: Constant Losses
Definition: Core losses, which occur 24/7 regardless of the transformer's load.
Term: Variable Losses
Definition: Copper losses, which depend on the square of the load current and are negligible at no-load.
"Average" Efficiency: Think of all-day efficiency as the "average" efficiency, not just the peak efficiency. It's the total energy over a long period.
"24/7" Transformers: It's for transformers that are always on, even when not working hard.
Losses Add Up: Core losses are like a fixed monthly fee (always there), while copper losses are like a variable usage charge (only when you use it). All-day efficiency sums up both.
Energy vs. Power: Remember it's about energy (kWh) over time, not just instantaneous power (kW).
Use mnemonics, acronyms, or visual cues to help remember key information more easily.
Think of all-day efficiency as the "average" efficiency, not just the peak efficiency. It's the total energy over a long period.
- "24/7" Transformers
Core losses are like a fixed monthly fee (always there), while copper losses are like a variable usage charge (only when you use it). All-day efficiency sums up both.
- Energy vs. Power
Review key concepts with flashcards.
Review the Definitions for terms.
Term: Energy Input (kWh)
Definition:
The total electrical energy consumed by the transformer from the source over a given time, including losses.
Term: Practical Implication
Definition:
Guides selection of transformers optimized for minimum lifetime energy consumption, often prioritizing lower core losses.
Term: Design Choice
Definition:
A utility needs a transformer for a residential area. Transformer A has 98% full-load efficiency but high core losses. Transformer B has 97.5% full-load efficiency but very low core losses. Transformer B is likely to have higher all-day efficiency and be a better choice, as residential loads are highly fluctuating.
Term: Definition
Definition:
Copper losses, which depend on the square of the load current and are negligible at no-load.
Term: Energy vs. Power
Definition: